ControlledEnvironmentalRooms-MDAndersonCancer.doc
SECTION 13 21 00 – Controlled Environmental rooms
GENERAL
RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General Conditions and Division?01 Specification Sections, apply to this Section.
Specifications throughout all Divisions of the Project Manual are directly applicable to this Section, and this Section is directly applicable to them.
SUMMARY
Furnish all labor, materials, equipment and services necessary to complete fabrication and installation of Controlled Environmental Rooms (CER). CER types included here are Cold Rooms, Incubator Rooms, and Wide-Range Rooms.
All major components shall have applicable UL, AMCA, NEMA, ASME, ANSI and AHRI certifications which include motors, compressors, evaporator fan and evaporator coils, water-cooled condensers or air-cooled condensers, humidification/dehumidification equipment, and control panel assemblies.
Deliver CER components to their final location, and complete assembly of CER in place by factory trained technician.
Furnish and install refrigeration piping, electrical power wiring, control wiring and connections to all devices which are an integral part of the CER.
Provide freestanding stainless steel wire shelving and wall mounted perforated (15 to 25 percent) stainless steel shelving as shown on construction drawings (including in-wall backing).
Start-up and field performance testing of CER shall be performed by factory trained technical personnel.
REFERENCE STANDARDS
The latest published edition and applicable addenda of a reference shall be applicable to this Project unless identified by a specific edition date:
ANSI/ASHRAE Standard 15 Safety Standard for Refrigeration Systems.
ANSI/ASHRAE Standard 90.1 Energy Standard for Buildings Except Low-Rise Residential Buildings.
ANSI/AHRI - 420 Performances Rating of Forced-Circulation Free-Delivery Unit Coolers for Refrigeration.
ANSI/AHRI - 540 Standard for Performance Rating of Positive Displacement Refrigerant Compressors and Compressor Un
您可能关注的文档
- Chapter12FourierSeries.PDF
- Chapter12HumanGenetics.ppt
- Chapter12MusculoskeletalInjuries(NXPowerLite)-Ronna.doc
- Chapter14-ListeningToTheSilences.doc
- Chapter18FossilFuelsandtheEnvironment-Sarasota.ppt
- Chapter1ComputingTools.ppt
- Chapter1EnvironmentalScience.doc
- Chapter1Notes-Preliminaries.doc
- Chapter1StudyQuestionswithAnswers.doc
- CHAPTER1UNDERSTANDINGOURENVIRONMENT.doc
文档评论(0)