experiment study on smoke movement leading to glass damages in double-skinned facade.pdf

experiment study on smoke movement leading to glass damages in double-skinned facade.pdf

  1. 1、本文档共11页,可阅读全部内容。
  2. 2、有哪些信誉好的足球投注网站(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
  3. 3、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载
  4. 4、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
查看更多
experiment study on smoke movement leading to glass damages in double-skinned facade

C/locate/conbuildmat Construction and Building Materials 21 (2007) 556–566 and Building MATERIALSExperimental study on smoke movement leading to glass damages in double-skinned fac?ade W.K. Chow a,*, W.Y. Hung a, Y. Gao b, G. Zou b, H. Dong b a Areas of Strength: Fire Safety Engineering, Research Centre for Fire Engineering, The Hong Kong Polytechnic University, Hong Kong, China b Department of Building Engineering, Harbin Engineering University, Harbin, Heilongjiang, China Received 5 January 2005; received in revised form 20 September 2005; accepted 22 September 2005 Available online 7 November 2005Abstract Fire hazard of the new architectural feature – double-skinned fac?ade was examined experimentally. Full-scale burning tests on part of the design feature were carried out in a facility developed in a remote area in Northeast China. A total of eight tests were performed to demonstrate how the depth of cavity of a double-skinned fac?ade affects the smoke movement. Surface temperature and heat flux received on the test panels are presented. Cracking patterns found on the glass panels are also observed. The measured results would give the possible smoke movement pattern inside the air cavity. By examining the results for cavity depth of 0.5, 1.0 and 1.5 m, it is found that a deeper cavity might give better safety under the scenario studied. The outer glass panel would be broken rapidly for the cavity of 0.5 m deep. Double-skinned fac?ade with a cavity of 1.0 m deep appeared to be very risky as glass panels above broke most among the different cavity depths. The inner glass panel might be broken before the outer panel. This would give an undesirable outcome. Other separation distances of the two skins should be further examined to give optimum design of cavity depth. Other factors affecting flame and smoke movement should be further investigated.  2005 Elsevier Ltd. All rights reserved. Keywords: Double-skinned fac?ade; Smoke movement; Cavity; Full-scale burning tes

文档评论(0)

l215322 + 关注
实名认证
内容提供者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档