StdmSmokeControl
11
SMOKE CONTROL
Ref.: BMC 23.10.045, IBC 909, IFC 909, NFPA 92A, 92B
11.01 Standards Established
11.01-1 Scope. The purpose of this standard is to clarify existing Code and City of
Bellevue Fire Department (BFD) requirements for the design, installation
and acceptance testing of smoke control systems. This information is to
supplement existing code requirements and does not cover all aspects.
This section applies to active and/or passive smoke control systems, and
includes shaft pressurization as well as zoned smoke control systems.
Questions or comments can be directed to the Assistant Fire Marshal- Plan
Review.
Design Approaches may include the Pressurization Method, Airflow
Design Method, Exhaust Method, Passive Smoke Control and Performance
Based Designs. All of these are defined in ICC standards. The objectives of
such designs is to accomplish the following:
(1) Contribute to the protection of life and to the reduction of property loss
(2) Provide conditions outside the event zone that enable emergency
response personnel to enter for rescue and fire-fighting operations
(3) Maintain a tenable environment in smoke refuge areas and exit
enclosures, and within the event zone when utilizing the exhaust
method, for the required duration
(4) Inhibit smoke from entering stairwells, smoke refuge areas, elevator
shafts, or similar areas
(5) Inhibit the migration of smoke from the event zone
11.01-2 Smoke control (when required). The IBC requires the following
smoke control systems:
(1) High-rise Buildings (403.13)
(2) When utilizing footnote (e) of Bellevue Amended Table 503 (503)
(3) Pressurized Shafts/Smokeproof Enclosures (1020.1.7)
(4) Underground Buildings (405.5)
(5) Building Atriums (404.4)
(6) Windowless Buildings (408.8)
(7) Stages and Platforms (410.3.7.2)
(8) Covered Mall Buildings (402.9)
(9) Assembly Seating (1025.6.2.1)
Page 1 of 38
11.01-3 Smoke control and smoke management systems shall comply with
IB
您可能关注的文档
- RED_ONE说明书.pdf
- Reinforced Mullion Joining Components (1990 to Present).pdf
- Reheating a multi-throat universe by brane motion.pdf
- relative valuation roles of equity book value and net income as a function of financial health第一期.pdf
- Rel-07_description_20100924.doc
- Relativistic corrections to the energy spectra of completely confined particles.pdf
- Relativistic mean-field description of the dynamics of giant resonances.pdf
- reliefvalve.pdf
- Removal of fluoride from drinking water by adsorption onto alum-impregnated activated alumina.pdf
- Removal of metal ions from aqueous solution by adsorption onto activated carbon clothsadsorption com.pdf
文档评论(0)