ASHRAE 2011 Liquid Cooling Guidelines for Data Centers
Data Center Education Series
Cooling Systems
Roger Schmidt
Sept, 2011
Data Center Education Series
ASHRAE New Thermal Guidelines
for Liquid Cooled Data Processing Environments
Roger Schmidt, IBM Fellow
Chief Engineer - Data Center Energy Efficiency
Prabjit Singh, STSM, Materials Lab
Agenda
ASHRAE’s New Liquid Cooled Guidelines
Infrastructure for Supporting IT Equipment
Other Guidelines - Wetted Materials Water Quality
References
One Year Anniversary of Data Center Ed. Series – some demographics
Q A
Data Center Education Series
Cooling Systems
Roger Schmidt
Sept, 2011
Reason for New Liquid Cooling Guidelines
Reduce number of chiller hours per year
Design data center w/o chillers
Very similar to Air Cooling Guidelines
where customers wanted wider
temperature and humidity guidelines
US National Labs wanted to run all their
HPC data centers w/o chillers being
required for entire year as an option
A Common Data Center Power Allocation
IT
Equipment
(46%)
Other (11%)
HVAC Cooling
(23%)
HVAC Fans (8%)
Lighting (4%) UPS (8%)
Data Center Education Series
Cooling Systems
Roger Schmidt
Sept, 2011
Liquid Cooling Loops for a Data Center
Rack
CDU
Chiller
Coolin
g
Tower
Load
Building
Datacom Equipment Center
Condenser
Water System
(CWS)
Technology
Cooling
Systems
(TCS)
Datacom
Equipment
Cooling
System
(DECS
Chilled
Water
System
(CHWS)
Reference: ASHRAE publication: Liquid Cooling Guidelines for Datacom Equipment Centers
/
X
Data Center Education Series
Cooling Systems
Roger Schmidt
Sept, 2011
Where are the Interface Requirements Defined?
Raised Floor
Foundation
Building
Return
Supply
Rack
or
Cabinet
External
CDU
Defined Interface
Requirements
AIRAIR
AIR AIR
Raised Floor
Foundation
Building
Return
Supply
Rack
or
Cabinet
Internal
CDU
Defined Interface
Requirements
4” copper pipe around perimeter
- Supply return
5” steel pipe Mechanical Room
-supply return
3” copper pipe through center
-supply return30 to 36” raised floor
Defined Interface
Requirements
D
您可能关注的文档
- AGN Feedback and Evolution of Radio Sources Discovery of an X-ray Cluster Associated with z.pdf
- Agreement between China and Ethiopia.pdf
- Agricultural price statistics in the Czech Republic.pdf
- Age and Metallicity Distribution of the Galactic Bulge from Extensive Optical and Near-IR S.pdf
- AHB2APB_DataSheet.pdf
- Airborne Noise Flanking of Shipboard Vibration.doc
- AIAA-44356-943.pdf
- Aircraft noise-abatement and mitigation strategies.pdf
- Airline Revenue Management and e-Markets Outline.pdf
- AJAX-Microsoft Translator V2 必应在线翻译API.pdf
文档评论(0)