IRIGB_对时信号
IRIG-B Time Code
IRIG-B Time Code
Although the synchronization bus can carry many forms of time signal, the IRIG-B time code is the most
widely used synchronization signal within substations. The basic form of IRIG-B consists of a pulse-width
modulated digital data stream at the rate of 100 pulses per second. The leading edge of each pulse is
precisely positioned in time on the incremental 10mS point within the second, while the pulse width
modulation conveys time and date information repeating within each 100 pulse frame i.e. once per second.
There are a number of variations of IRIG-B time codes in common use. IRIG-B time codes are defined using
a 4-character descriptor: B x y z, and x, y and z have meaning as follows:
B x y z
[format] [modulation type] [frequency/resolution] [coded expression]
B denotes IRIG-B
x designator, modulation type has three possible values:
0 = Unmodulated, also called DC level shift
1 = Amplitude Modulated (AM) sine wave
2 = Modified Manchester modulated
The y designator, frequency/resolution has values as follows:
0 = no carrier / index count interval (commonly used with IRIG-B)
1 = 100Hz carrier (not used with IRIG-B)
2 = 1000Hz carrier (commonly used with IRIG-B)
The z designator, coded expression has values as follows:
0 = BCD, CF, SBS
1 = BCD, CF
2 = BCD
3 = BCD, SBS
BCD = Binary Coded Decimal format = basic time-of-year information (does not include year information).
CF = Control Function = additional information including year information (eg IEEE1344 extensions or
AFNOR extensions).
SBS = Straight Binary Seconds = seconds-of-day in binary format.
The valid combinations in use for IRIG-B are: B00z, B12z and B22z.
B00z (DC level-shift IRIG-B)
B00z (DC level-shift IRIG-B) has been favored fo
您可能关注的文档
最近下载
- LittleSwan小天鹅小天鹅10KG滚筒洗干一体机 巴赫银 转速1400.0 带银离子 TD100VT616WIADY.pdf
- 领域数据空间如何破解数据可信流通.pptx VIP
- 三菱车系发动机数据流说明手册.pdf VIP
- 交通银行流水.xls VIP
- 《城镇燃气燃烧器具销售和售后服务要求》专题培训.pptx
- 2025华医网继续教育危重症患者气道精细化管理题库答案.docx VIP
- 秋季营销全攻略.pptx VIP
- 重塑数据可信流通数据空间:理论、架构与实践_札记.docx VIP
- 关于进一步加强医院劳动纪律的通知5则范文.pdf VIP
- 部编人教版语文六年级下册语文全册教案(2023年1月修订).pdf
文档评论(0)