网站大量收购闲置独家精品文档,联系QQ:2885784924

数字式检测装置相位误差量值溯源方法研究.pdfVIP

数字式检测装置相位误差量值溯源方法研究.pdf

  1. 1、本文档共7页,可阅读全部内容。
  2. 2、有哪些信誉好的足球投注网站(book118)网站文档一经付费(服务费),不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
  3. 3、本站所有内容均由合作方或网友上传,本站不对文档的完整性、权威性及其观点立场正确性做任何保证或承诺!文档内容仅供研究参考,付费前请自行鉴别。如您付费,意味着您自己接受本站规则且自行承担风险,本站不退款、不进行额外附加服务;查看《如何避免下载的几个坑》。如果您已付费下载过本站文档,您可以点击 这里二次下载
  4. 4、如文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“版权申诉”(推荐),也可以打举报电话:400-050-0827(电话支持时间:9:00-18:30)。
  5. 5、该文档为VIP文档,如果想要下载,成为VIP会员后,下载免费。
  6. 6、成为VIP后,下载本文档将扣除1次下载权益。下载后,不支持退款、换文档。如有疑问请联系我们
  7. 7、成为VIP后,您将拥有八大权益,权益包括:VIP文档下载权益、阅读免打扰、文档格式转换、高级专利检索、专属身份标志、高级客服、多端互通、版权登记。
  8. 8、VIP文档为合作方或网友上传,每下载1次, 网站将根据用户上传文档的质量评分、类型等,对文档贡献者给予高额补贴、流量扶持。如果你也想贡献VIP文档。上传文档
查看更多
数字式检测装置相位误差量值溯源方法研究.pdf

Smart Grid 智能电网, 2016, 6(6), 353-359 Published Online December 2016 in Hans. /journal/sg /10.12677/sg.2016.66039 Research on Method for Phase Accuracy Measurement Traceability of Digital Test Equipment Ming Lei, Yue Guo, Yingchun Wang, Lieqi Yan, Xin Zheng Metrology Centre of Hubei Electric Power Company, Wuhan Hubei th th th Received: Oct. 18 , 2016; accepted: Nov. 12 , 2016; published: Nov. 15 , 2016 Copyright © 2016 by authors and Hans Publishers Inc. This work is licensed under the Creative Commons Attribution International License (CC BY). /licenses/by/4.0/ Open Access Abstract Electronic instrument transformers (EIT) and merging units (MU) are widely utilized in the smart substations, and EIT testers and MU testers are used to test the accuracy of EITs and MUs. The EIT tester calibrator can calibrate the accuracy of the equipment. However, the accuracy of calibrator, especially the phase accuracy, cannot be traced to the existing standards due to the lack of appro- priate method, thus causing the incompleteness of the accuracy tracing system. Therefore, the EITs and MUs running in the smart substations cannot be used as electric power measurement equipment. In order to solve this problem, a method to calibrate the phase accuracy of the digital equipment is proposed in this paper. Compared to the currently used method based on digital mi- cro-difference source, this method can trace the phase accuracy of EITs and MUs to a precise time standard. This method provides the technical basis for the smart equipment’s utilization as me- trological devices. Keywords Phase Accuracy, Electronic Instrument Transformer, M

文档评论(0)

zhoujiahao + 关注
实名认证
文档贡献者

该用户很懒,什么也没介绍

1亿VIP精品文档

相关文档