数字式检测装置相位误差量值溯源方法研究.pdf
Smart Grid 智能电网, 2016, 6(6), 353-359
Published Online December 2016 in Hans. /journal/sg
/10.12677/sg.2016.66039
Research on Method for Phase Accuracy
Measurement Traceability of Digital
Test Equipment
Ming Lei, Yue Guo, Yingchun Wang, Lieqi Yan, Xin Zheng
Metrology Centre of Hubei Electric Power Company, Wuhan Hubei
th th th
Received: Oct. 18 , 2016; accepted: Nov. 12 , 2016; published: Nov. 15 , 2016
Copyright © 2016 by authors and Hans Publishers Inc.
This work is licensed under the Creative Commons Attribution International License (CC BY).
/licenses/by/4.0/
Open Access
Abstract
Electronic instrument transformers (EIT) and merging units (MU) are widely utilized in the smart
substations, and EIT testers and MU testers are used to test the accuracy of EITs and MUs. The EIT
tester calibrator can calibrate the accuracy of the equipment. However, the accuracy of calibrator,
especially the phase accuracy, cannot be traced to the existing standards due to the lack of appro-
priate method, thus causing the incompleteness of the accuracy tracing system. Therefore, the
EITs and MUs running in the smart substations cannot be used as electric power measurement
equipment. In order to solve this problem, a method to calibrate the phase accuracy of the digital
equipment is proposed in this paper. Compared to the currently used method based on digital mi-
cro-difference source, this method can trace the phase accuracy of EITs and MUs to a precise time
standard. This method provides the technical basis for the smart equipment’s utilization as me-
trological devices.
Keywords
Phase Accuracy, Electronic Instrument Transformer, M