茂县潘达尔硅业有限公司2×33MVA工业硅矿热炉余热发电工程 补给水系统调试方案
目
1、系统简介·······················································2
2、编制依据·······················································2
3、主要设备参数及规范···········································2-4
4、调试前各项条件基本具备·······································4-5
5、调试步骤·····················································5-8
6、调试结果····················································8-9
7、安全措施·······················································9
8、组织分工·······················································9
焦作市新思源电力工程有限公司 1
茂县潘达尔硅业有限公司2×33MVA工业硅矿热炉余热发电工程 补给水系统调试方案
1.系统简介
1.1 系统选择:
根据设计、规程、规范要求和机、炉参数、水汽质量标准以及水源水质情况,锅炉补给
水处理方式,采用多介质过滤器、活性炭过滤器、一级反渗透、二级反渗透加上EDI 装置的
除盐系统。系统采用串联母管制运行连接方式.设计出力10t /h。
1.2 系统介绍
1.2.2 补给水系统流程
本工程补给水系统流程为:
水库地表水—化学原水箱—化学原水泵一多介质过滤器一活性炭过滤器一保安过滤器—一级
反渗透高压泵—一级反渗透—缓冲水箱一二级反渗透高压泵—二级反渗透一中间水箱一中间
水泵一EDI 装置一除盐水箱一除盐水泵一除氧器。
1.2.3 补给水系统出水的水质
硬 度:≈0umol /L
二氧化硅:≤100ug /L;
1.2.4 控制水平与运行方式
本工程化学补给水系统的运行一二级反渗透及EDI 装置采用自动连锁模式,设自动、手
动操作两种控制方式。
各水箱高、中、低水位信号,水位到达低位或高位一、二级反渗透及EDI 装置将自动停
机保护。
2 编制依据
《电力建设施工及验收技术规范》第四部分 电厂化学 DL/T5190 4
《火力发电厂化学设计技术规程》DL/T5068
《火力发电厂化学调试导则》DL/T1076
《中材节能股份有限公司发电机组设计方案补给水部分》
3 主要设备参数及规范
3.1 设备参数
设备 单
多介质过滤器 活性炭过滤器 一级反渗透 二级反渗透 EDI
名称 位
数 量 台 1 1 1 套 1 套 2 块
焦作市新思源电力工程有限公司 2
茂县潘达尔硅业有限公司2×33MVA工业硅矿热炉余热发电工程 补给水系统调试方案
材
碳钢 碳钢
质
设计
MPa 0.6 0.6 1.5 1.5 0.6
压力
介
水 水 水 水 水
质
工作
℃ 5—30 5—30 常温 常温 常温
温度
设计
m/h 10 10
流速
设计
文档评论(0)